Mini Sensor Controlled Relay
The device allows you to adjust the voltage level of the signal.
The mini relay box with optional voltage output can be connected to the RAMOS Optimax or RAMOS Plus main monitoring units.
This device can adjust the voltage level of the signal, for example, a device with a relay can be switched based on the sensor input, then this output from the sensor will be 200 mA—5 V DC.
Order code: RMS-P-RB
Parameter | Value |
---|---|
Coil consumption | 150 mW |
Switching power | 120VA, 24W |
Contact material | AgNi alloy |
Minimum contact load | 1mA @ 1V DC |
Initial contact resistance | 50mΩ u 100mA, 6V DC |
Contact load | 1A, 120 VAC / 24 V DC |
Mechanical resistance | 10x10e6 operations |
Electrical resistance | 1A, 120 VAC, resistance 100x10e3 ops. |